Oak Bluffs, MA old classifieds archive and funnies   >   Industrial Machines   >   New omron power supply in box S82K-10024 24VDC

New omron power supply in box S82K-10024 24VDC


100 to 120 VAC (85 to 132 VAC)
200 to 240 VAC (170 to 264 VAC)
50/60Hz (47 to 450 Hz Single-phase)
0.5 mA Max. (At 100 VAC input)
25 A Max. (At 100 VAC input (For cold start at 25 CEL))
50 A Max. (At 200 VAC input (For cold start at 25 CEL))
(The output voltage may increase beyond the allowable voltage range (up to +10% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.)
2%(p-p) Max. (Under the rated I/O conditions.)
Static input variation influence
0.5% Max. (At 85 to 132 VAC/170 to 264 VAC input, 100% load)
Static load variation influence
1.5 % Max. (At rated input, 0 to 100% load)
Ambient temperature variation influence
0.05%/ CEL Max.(At rated input/output voltage)
200 ms Max. (At rated input/output voltage)
20 ms Min. (At rated input/output voltage)
Inverted L voltage drop, automatic reset
Maintenance forecast monitor output
Yes (NC relay output), 24 VDC, 0.1 A
Yes (Up to 2 Power Supplies with external diode)
Standard No.: UL508(Listing, Class2 :Per UL1310)
Standard No.: CSA C22.2 No.14(Class 2 : Per No.223), CSA No.60950-1
Standard No.: EN50178, EN60950-1
Applicable standard (EC Directive (EMC Directive))
Emission Enclosure: Conforms to EN61204-3 ClassB
Emission AC mains: Conforms to EN61204-3 Class B, Based on FCC Class A
Standard No.: VDE0160, VDE0805 Teil 1
Conformed standard 2: VDE0106 /P100
Operating: -10 to 60 CEL (Refer to the Derating curve)
(with no icing or condensation)
Between all inputs and all outputs: 3 kVAC for 1 min (Cut-off current: 20 mA)
Between all inputs and PE terminals: 2 kVAC for 1 min (Cut-off current: 20 mA)
Between all outputs and PE terminals: 1 kVAC for 1 min (Cut-off current: 20 mA)
Between all outputs and all inputs/PE terminals: 100 M Ohm Min. (at 500 VDC)
10 to 55 Hz, 0.375mm single amplitude for 2 h each in X, Y, Z directions
300 m/s2, 3 times each in +- X, +- Y, and +- Z directions
My Stores Logo S/H is Calculated



New omron power supply in box S82K-10024 24VDC